[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937526":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937526,605,2,"多选题","消防增（稳）压设施由消防稳压泵和消防稳压罐组成。气压水罐上应设有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","水位指示器",true,{"key":16,"text":17,"correct":14},"B","安全阀",{"key":19,"text":20,"correct":14},"C","压力开关或压力变送器",{"key":22,"text":23,"correct":24},"D","真空表",false,{"key":26,"text":27,"correct":14},"E","泄水管","ABCE","2020新教材P151 “气压罐有效容积、气压、水位及工作压力符合设计要求；气压水罐应有水位指示器；气压水罐上的安全阀、压力表、泄水管、压力控制仪表等符合产品使用说明书的要求”，参考《消防给水及消火栓系统技术规范》11.0.6：“稳压泵应由消防给水管网或气压水罐上设置的稳压泵自动启停泵压力开关或压力变送器控制”，故A、B、C、E正确，D错误，应为压力表，而不是真空表。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]