[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937522":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937522,605,2,"多选题","消防水泵检测验收时，应启动消防泵进行测试，下列说法中正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","消防水泵启动控制按钮应置于手动启动挡",false,{"key":16,"text":17,"correct":18},"B","打开消防水泵出水管上试水阀，当采用主电源启动消防水泵时，消防水泵应启动正常",true,{"key":20,"text":21,"correct":18},"C","打开消防水泵出水管上试水阀，关掉主电源，主、备电源应能正常切换",{"key":23,"text":24,"correct":18},"D","消防水泵就地和远程启\u002F停功能应正常，并向消防控制室反馈状态信号",{"key":26,"text":27,"correct":18},"E","消防水泵运转应平稳，应无不良噪声的振动","BCDE","2020新教材P160 A应位于“自动启动挡”，方能在打开试水阀的时候自动启动，也才能在远程启、停水泵，故A错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]