[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937521":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937521,605,2,"多选题","下列关于消防水泵的检测验收要求中，正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","消防水泵运转应平稳，应无不良噪声的振动",true,{"key":16,"text":17,"correct":14},"B","对照图样，检查工作泵、备用泵、吸水管、出水管及出水管上泄压阀、水捶消除设施、止回阀、信号阀等的规格、型号、数量，应符合设计要求",{"key":19,"text":20,"correct":21},"C","吸水管、出水管上的控制阀应锁定在常闭位置，并有明显标记",false,{"key":23,"text":24,"correct":14},"D","分别开启系统中的每一个末端试水装置、试水阀和试验消火栓，水流指示器、压力开关、低压压力开关、高位消防水箱流量开关等信号的功能，均符合设计要求",{"key":26,"text":27,"correct":21},"E","在阀门出口用压力表检查消防水泵停泵时，水锤消除设施后的压力不应超过水泵出口设计额定压力的1.2倍","ABD","2020新教材P160 ]消防水泵的检测验收要求：1.吸水管、出水管上的控制阀应锁定在常开位置，井有明显标记。C错误 2.在间门出口用压力表检查消防水泵停泵时，水锤消除设施后的压力不应超过水泵出口设计额定压力的1.4倍。E错误",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]