[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937502":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937502,605,2,"多选题","消防给水及消火栓系统管网施工时，应设防晃支架的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","管道管径为DN70的四通位置处",true,{"key":16,"text":17,"correct":14},"B","管径为DN100的管道拐弯处",{"key":19,"text":20,"correct":14},"C","管径为DN80的管道三通位置处",{"key":22,"text":23,"correct":24},"D","管径为DN40的配水管中点处",false,{"key":26,"text":27,"correct":14},"E","管径为DN80的配水管中点处","ABCE","2020新教材P169 下列部位应设置固定支架或防晃支架： 1）配水管宜在中点设一个防晃支架，但当管径小于DN50时可不设。 2）配水干管及配水管，配水支管的长度超过15m，每15m长度内应至少设1个防晃支架，但当管径不大于DN40可不设。 3）管径大于DN50的管道拐弯、三通及四通位置处应设1个防晃支架。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]