[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937496":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937496,605,2,"多选题","海南某四层商业建筑消防验收中，下列关于泵接合器的检查和安装的说法中正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","组装式水泵接合器组件中，止回阀的安装方向从接口指向控制阀方向",true,{"key":16,"text":17,"correct":18},"B","地上式水泵接合器安装在接近机动车道的位置",false,{"key":20,"text":21,"correct":18},"C","水泵接合器与室外消火栓的距离为10m",{"key":23,"text":24,"correct":18},"D","某墙壁水泵接合器安装高度距地面1.1m",{"key":26,"text":27,"correct":14},"E","某墙壁水泵接合器安装位置距离墙面门窗洞口的净距为2m","AE","2020新教材P161 选项A，组装式水泵接合器的安装，应按接口、本体、连接管、止回阀、安全阀、放空管、控制阀的顺序进行，止回阀的安装方向应使消防用水能从水泵接合器进人系统，整体式水泵接合器的安装按其使用安装说明书进行。故A正确；选项B、C，水泵接合器接口的位置应方便操作，安装在便于消防车接近的人行道或非机动车行驶地段，距离室外消火拴或消防水池的距离宜为15~40m。故B、C错误。选项D、E，墙壁水泵接合器的安装应符合设计要求。设计无要求时，其安装高度距地面宜为0.7m；与墙面上的门、窗、孔、洞的净距离不应小于2.0m，且不应安装在玻璃幕墙下方。故D错误，E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]