[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937490":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937490,605,1,"单选题","某民用建筑的消火栓系统施工完毕后，对其进行试压和冲洗，下列关于消火栓系统试压和冲洗的要求，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","水压强度试验对管网注水时，应将管网内的空气排净，并应缓慢升压，达到试验压力后，稳压30min后，管网应无泄漏、无变形，且压力降不应大于0.01MPa",false,{"key":16,"text":17,"correct":14},"B","气压严密性试验的介质宜采用空气或氮气，试验压力应为0.28MPa，且稳压24h，压力降不应大于0.05MPa",{"key":19,"text":20,"correct":21},"C","水压强度试验的测试点应设在系统管网的最低点",true,{"key":23,"text":24,"correct":14},"D","水压严密性试验应在水压强度试验和管网冲洗合格后进行，试验压力应为系统工作压力，稳压48h，应无泄漏","2020新教材P169 水压强度试验的测试点应设在系统管网的最低点。对管网注水时，应将管网内的空气排净，并应缓慢升压，达到试验压力后，稳压30min后，管网应无泄漏、无变形，且压力降不应大于0.05MPa，A选项错误，C选项正确；根据12.4.7，气压严密性试验的介质宜采用空气或氮气，试验压力应为0.28MPa，且稳压24h，压力降不应大于0.01MPa，B选项错误；根据12.4.4，水压严密性试验应在水压强度试验和管网冲洗合格后进行。试验压力应为系统工作压力，稳压24h，应无泄漏，D选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]