[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937488":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937488,605,1,"单选题","下列关于消防水池和消防水箱的施工安装要求的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防水池和消防水箱出水管或水泵吸水管应满足最低有效水位出水不掺气的技术要求",true,{"key":16,"text":17,"correct":18},"B","钢板等制作的消防水池和消防水箱的进出水等管道应加设防水套管",false,{"key":20,"text":21,"correct":18},"C","钢筋混凝土制作的消防水池和消防水箱的进出水等管道宜采用法兰连接",{"key":23,"text":24,"correct":18},"D","消防水池、消防水箱的溢流管、泄水管应与生产或生活用水的排水系统直接相连","2020新教材P156 1）消防水池和消防水箱出水管或水泵吸水管应满足最低有效水位出水不掺气的技术要求。 2）钢筋混凝土制作的消防水池和消防水箱的进出水等管道应加设防水套管，钢板等制作的消防水池和消防水箱的进出水等管道宜采用法兰连接，对有振动的管道应加设柔性接头。组合式消防水池或消防水箱的进水管、出水管接头宜采用法兰连接，采用其他连接时应做防锈处理。 3）消防水池、消防水箱的溢流管、泄水管不应与生产或生活用水的排水系统直接相连，应采用间接排水方式。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]