[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937389":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937389,605,2,"多选题","引入用户信息传输装置的电缆或导线，应符合（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","配线应整齐，不宜交叉，并应固定牢靠",true,{"key":16,"text":17,"correct":14},"B","端子板的每个接线端，接线不得超过2根",{"key":19,"text":20,"correct":21},"C","电缆芯和导线，应留有不小于150mm的余量",false,{"key":23,"text":24,"correct":14},"D","导线应绑扎成束",{"key":26,"text":27,"correct":21},"E","导线穿管、线槽后，不应将管口、槽口封堵","ABD","2020新教材P450 引入用户信息传输装置的电缆或导线，应符合下列要求: （ 1 ）配线应整齐，不宜交叉，并应固定牢靠。 （ 2 ）电缆芯线和所配导线的端部，均应标明编号，并与图样一致，字迹应清晰且不易褪色。 （ 3 ）端子板的每个接线端，接线不得超过 2 根。 （4） 电缆芯线和导线，应留有不小于 200mm 的余量。 （ 5 ）导线应绑扎成束。 （ 6 ）导线穿管或穿线槽后，应将管口、槽口封堵。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]