[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937369":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937369,605,2,"多选题","火灾自动报警系统的线管在超过一定长度时，应在便于接线处装设接线盒，下列部位应设置接线盒的有（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","管子直线段长度超过30m",true,{"key":16,"text":17,"correct":14},"B","管子长度超过20m，有1个弯曲",{"key":19,"text":20,"correct":14},"C","管子长度超过10m，有2个弯曲",{"key":22,"text":23,"correct":14},"D","管子长度超过8m，有3个弯曲",{"key":25,"text":26,"correct":27},"E","管子长度超过15m，有1个弯曲",false,"ABCD","2020新教材P402 管路超过下列长度时，应在便于接线处装设接线盒：1）管子长度每超过30m，无弯曲时。2）管子长度每超过20m，有1个弯曲时。3）管子长度每超过10m，有2个弯曲时。4）管子长度每超过8m，有3个弯曲时。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]