[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937367":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937367,605,2,"多选题","火灾自动报警系统管路超过一定长度时，应在便于接线处装设接线盒，下列情况要在接线处装设接线盒的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","管长每超过30m，无弯曲",true,{"key":16,"text":17,"correct":14},"B","管长每超过20m，有1个弯曲",{"key":19,"text":20,"correct":21},"C","管长15m，有1个弯曲",false,{"key":23,"text":24,"correct":14},"D","管长每超过10m，有2个弯曲",{"key":26,"text":27,"correct":21},"E","管长每超过9m，有2个弯曲","ABD","2020新教材P403 符合管子长度每超过30m，无弯曲时；管子长度每超过20m，有1个弯曲时；管子长度每超过10m，有2个弯曲时；管子长度每超过8m，有3个弯曲时等装设接线盒。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]