[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937359":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937359,605,1,"单选题","消防技术服务机构对某图书馆内的火灾自动报警系统进行检测，发现了如下情况，其中不符合现行国家消防技术标准的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","设在封闭楼梯间入口附近的声光警报器与安全出口标志灯相距1m",true,{"key":16,"text":17,"correct":18},"B","图书阅览室内的声光警报器挂墙设置，距地高度为2.3m",false,{"key":20,"text":21,"correct":18},"C","实测图书阅览室内的声光警报器声压为70dB",{"key":23,"text":24,"correct":18},"D","在疏散走道转角处设置有声光警报器，楼梯间内未设置","2020新教材P408 光警报器与消防应急疏散指示标志不宜在同一面墙上，安装在同一面墙上时，距离应大于1m，A选项错误；根据《火灾自动报警系统设计规范》GB 50116 - 2013 6.5.3，当火灾警报器采用壁挂方式安装时，其底边距地面高度应大于2.2m，B选项正确；根据6.5.2，每个报警区域内应均匀设置火灾警报器，其声压级不应小于60dB；在环境噪声大于60dB的场所，其声压级应高于背景噪声15dB，C选项正确；根据6.5.1，火灾光警报器应设置在每个楼层的楼梯口、消防电梯前室、建筑内部拐角等处的明显部位，且不宜与安全出口指示标志灯具设置在同一面墙上，D选项正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]