[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937356":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937356,605,1,"单选题","下列关于点型感烟、感温火灾探测器安装要求的叙述中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","探测器至墙壁、梁边的水平距离，不应小于0.5m",false,{"key":16,"text":17,"correct":14},"B","探测器周围水平距离0.5m内，不应有遮挡物",{"key":19,"text":20,"correct":21},"C","探测器至空调送风口最近边的水平距离，不应小于0.5m",true,{"key":23,"text":24,"correct":14},"D","探测器至多孔送风顶棚孔口的水平距离，不应小于0.5m","2020新教材P405 （ 1 ）探测器至墙壁、梁边的水平距离，不应小于 0.5 m 探测器周围水平距离 0.5 m 内，不应有遮挡物探测器至空调送风口最近边的水平距离，不应小于1.5 m 至多孔送风顶棚孔口的水平距离，不应小于 0 .5 m,（ 2 ）在宽度小于 3m 的内走道顶棚上安装探测器时，宜居中安装。点型感温火灾探测器的安装间距不应超过 10m 点型感烟火灾探测器的安装间距不应超过 15 m 。 探测器至端墙的距离不应大于安装间距的一半 。（3）探测器宜水平安装，当确实需倾斜安装时，倾斜角不应大于 45 °",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]