[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937355":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937355,605,1,"单选题","任意一台消防联动控制器地址总数或火灾报警控制器（联动型）所控制的各类模块总数不应超过（ ）点，每一联动总线回路连接的设备总数不宜超过（ ）点，且应保留不少于额定容量（ ）的余量。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1200,200,20%",false,{"key":16,"text":17,"correct":14},"B","1500,100,20%",{"key":19,"text":20,"correct":21},"C","1600,100,10%",true,{"key":23,"text":24,"correct":14},"D","1800,200,10%","《火灾自动报警系统设计规范》（GB50116-2013） 3.1.5：“任一台火灾报警控制器所连接的火灾探测器、手动火灾报警按钮和模块等设备总数和地址总数，均不应超过3200点，其中每一总线回路连接设备的总数不宜超过200点，且应留有不少于额定容量10%的余量：任一台消防联动控制器地址总彰或火灾报警控制器（联动型）所控制的各类模块总数不应超过1600点，每一联动总线回路连接设备的总数不宜超过100点，且应留有不少于额定容量10%的余量”，故C正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]