[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937354":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937354,605,1,"单选题","某建筑高度为128m的民用建筑内设置的火灾自动报警系统，需要配备总数为1600点的联动控制模块，故应至少选择（ ）台消防联动控制器或联动型火灾报警控制器。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":14},"B","3",{"key":19,"text":20,"correct":21},"C","2",true,{"key":23,"text":24,"correct":14},"D","4","《火灾自动报警系统设计规范》（GB50116-2013） 3.1.5：“任一台消防联动控制器地址总数或火灾报警控制器（联动型）所控制的各类模块总数不应超过1600点，每一联动总线回路连接设备的总数不宜超过100点，且应留有不少于额定容量10%的余量”，故1600个点应至少选择2台消防联动控制器或联动型火灾报警控制器，故C正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]