[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937334":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937334,605,2,"多选题","下列火灾自动报警系统组件安装在墙上时，其安装高度要求均一致的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","手动火灾报警按钮",true,{"key":16,"text":17,"correct":14},"B","区域显示器",{"key":19,"text":20,"correct":21},"C","消防应急广播扬声器",false,{"key":23,"text":24,"correct":14},"D","消防电话",{"key":26,"text":27,"correct":21},"E","防火门监控器手动按钮","ABD","2020新教材P407 手动火灾报警按钮应安装在明显和便于操作的部位。当安装在墙上时，其底边距地（楼）面高度宜为1.3～1.5m。根据3.3.1，火灾报警控制器、可燃气体报警控制器、区域显示器、消防联动控制器等控制器类设备在墙上安装时，其底边距地（楼）面高度宜为1.3～1.5m，其靠近门轴的侧面距墙不应小于0.5m，正面操作距离不应小于1.2m；落地安装时，其底边宜高出地（楼）面0.1～0. 2m。根据3.9.1，消防电话、电话插孔、带电话插孔的手动报警按钮宜安装在明显、便于操作的位置；当在墙面上安装时，其底边距地（楼）面高度宜为1.3～1.5m。根据《火灾自动报警系统设计规范》GB 50116 - 2013 6.6.2，壁挂扬声器的底边距地面高度应大于2.2m。根据6.11.2，电动开门器的手动控制按钮应设置在防火门内侧墙面上，距门不宜超过0. 5m，底边距地面高度宜为0.9m～1.3m。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]