[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937327":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937327,605,2,"多选题","火灾自动报警系统布线过程中，若管路敷设出现下列现象，应在便于接线处装设接线盒的是（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","管子长度每超过30m，无弯曲时",true,{"key":16,"text":17,"correct":14},"B","管子长度每超过20m，有1个弯曲时",{"key":19,"text":20,"correct":14},"C","管子长度每超过1Om，有2个弯曲时",{"key":22,"text":23,"correct":14},"D","管子长度每超过8m，有3个弯曲时",{"key":25,"text":26,"correct":27},"E","管子长度每超过5m，有2个弯曲时",false,"ABCD","2020新教材P402 管路超过下列长度时，应在便于接线处装设接线盒：①管子长度每超过30m，无弯曲时。故A正确；②管子长度每超过20m，有1个弯曲时。故B正确：③管子长度每超过1Om，有2个弯曲时。故C正确：④管子长度每超过8m，有3个弯曲时。故D正确，E错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]