[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937325":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937325,605,1,"单选题","某单位消防控制室内的火灾报警控制器发出故障报警，通讯故障灯亮，首先可以排除的原因是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","通讯线路短路、开路",false,{"key":16,"text":17,"correct":14},"B","通讯接口板损坏",{"key":19,"text":20,"correct":14},"C","火灾显示盘损坏",{"key":22,"text":23,"correct":24},"D","备用电源损坏或电压不足",true,"2020新教材P443 常见通讯故障原因：区域报警控制器或火灾显示盘损坏或未通电、开机；通讯接口板损坏；通讯线路短路、开路或接地性能不良造成短路。备用电源损坏或电压不足是备用电源常见故障，此时火灾报警控制器发出故障报警、备用电源故障灯亮。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]