[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937320":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937320,605,1,"单选题","下列关于缆式线型感温火灾探测器安装的说法，不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","探测器在电缆桥架内的电缆表面呈蛇形敷设",false,{"key":16,"text":17,"correct":14},"B","探测器设置在皮带输送机传送带滚轮下方",{"key":19,"text":20,"correct":14},"C","探测器设置在技术夹层顶棚下方，至顶棚的距离为0.1m",{"key":22,"text":23,"correct":24},"D","设置在顶棚下方的探测器弯折敷设，各段之间距离为3.5m",true,"2020新教材P405 探测器在保护电缆、堆垛等类似保护对象时，应采用接触式布置；在各种皮带输送装置上设置时，宜设置在装置的过热点附近，为增加探测器与电缆的接触，探测器在电缆表面呈蛇形弯折敷设，AB选项正确；根据6.2.6 -2，设置在顶棚下方的线型感温火灾探测器，至顶棚的距离宜为0.1m，探测器的保护半径应符合点型感温火灾探测器的保护半径要求；探测器至墙壁的距离宜为1m ~1.5m，根据《火灾自动报警系统设计规范图示》14X505 -1 6.2.16图示，设置在顶棚下方的探测器弯折敷设，各段之间距离最低为7.2m，即应满足点型感温火灾探测器的保护半径3. 6m的要求（3.6×2 =7.2m），C选项正确，D选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]