[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937318":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937318,605,1,"单选题","消防技术服务机构对某单位内的火灾自动报警系统进行检测，发现如下情况，其中不符合现行国家消防技术标准的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","办公室顶棚居中设置感烟火灾探测器",false,{"key":16,"text":17,"correct":14},"B","发电机房设置点型感温火灾探测器",{"key":19,"text":20,"correct":14},"C","会议室设置的点型感烟火灾探测器距空调送风口2m",{"key":22,"text":23,"correct":24},"D","储藏间设置的点型感烟火灾探测器贴梁安装在其侧面",true,"2020新教材P405 饭店、旅馆、教学楼、办公楼的厅堂、卧室、办公室、商场、列车载客车厢等宜选择点型感烟火灾探测器，A选项正确；根据3.2.3，厨房、锅炉房、发电机房、烘干车间等不宜安装感烟火灾探测器的场所宜选择点型感温火灾探测器，B选项正确；根据《火灾自动报警系统施工及验收规范》GB 50166 -2007 3.4.1-3，探测器至空调送风口最近边的水平距离，不应小于1.5m;至多孔送风顶棚孔口的水平距离，不应小于0.5m，C选项正确；根据3.4.1-5，探测器宜水平安装，当确需倾斜安装时，倾斜角不应大于45°，探测器安装在梁的侧面等于90°安装，D选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]