[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937298":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},937298,605,1,"单选题","某地下车库设置点型感烟火灾探测器，车库未做吊顶。则探测器布置时当梁突出顶棚的高度小于（ ）mm时，可不计梁对探测器保护面积的影响；当梁突出顶棚的高度超过（ ）mm时，被梁隔断的每个梁间区域应至少设置一只探测器。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","300,500",false,{"key":16,"text":17,"correct":18},"B","200,600",true,{"key":20,"text":21,"correct":14},"C","200,500",{"key":23,"text":24,"correct":14},"D","300,600","《火灾自动报警系统设计规范》（GB50116-2013） 6.2.3：“在有梁的顶棚上设置点型感烟火灾探测器、感温火灾探剧器时，映符合下列规定：1当梁突出顶棚的高度小于200mm时，可不计梁对探测器保护面积的影响。3当梁突出顶棚的高度超过600mm时，被梁隔断的每个梁间区域应至少设置一只探测器”，故B正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]