[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937288":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937288,605,1,"单选题","下列关于消防应急照明控制器安装的说法，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","应急照明控制器端子板的每个接线端，接线不得超过3根",false,{"key":16,"text":17,"correct":14},"B","应急照明控制器的主电源应设置明显的永久性标识，并应直接与消防电源连接，外接备用电源可采用电源插头连接",{"key":19,"text":20,"correct":21},"C","端子板连接的电缆芯和导线，应留有不小于200mm的余量",true,{"key":23,"text":24,"correct":14},"D","应急照明控制器在电气竖井内安装时，应采用上出口进线方式","2020新教材P387 应急照明控制器端子板的每个接线端，接线不得超过2根，A选项错误；根据4.4.3，应急照明控制器的主电源应设置明显的永久性标识，并应直接与消防电源连接，严谨使用电源插头；应急照明控制器与其外接备用电源之间应直接连接连接，B选项错误；根据4.4.5-4，应急照明控制器的接线线缆应留有不小于200mm的余量，C选项正确；根据4.4.1-4，应急照明控制器在电气竖井内安装时，应采用下出口进线方式，D选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]