[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937267":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937267,605,2,"多选题","为防止火灾通过消防用电设备供电线路传输，应对消防用电设备供电线路采取防火封堵措施，下列部位需要采取防火封堵措施是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","电缆桥架沿竖井垂直敷设穿越楼板处",true,{"key":16,"text":17,"correct":18},"B","电缆隧道每隔30m处",false,{"key":20,"text":21,"correct":14},"C","电缆引至配电柜、控制柜的开孔部位",{"key":23,"text":24,"correct":14},"D","电缆穿越电缆沟的隔墙处",{"key":26,"text":27,"correct":14},"E","管线进出竖井处","ACDE","2020新教材P368 消防用电设备供电线路在电缆隧道、电缆桥架、电缆竖井、封闭式母线、线槽安装等处时，在下列情况下应采取防火封堵措施。1）穿越不同的防火分区。2）沿竖井垂直敷设穿越楼板处。3）管线进出竖井处。4）电缆隧道、电缆沟、电缆间的隔墙处。5）穿越建筑物的外墙处。6）至建筑物的入口处，至配电间、控制室的沟道入口处。7）电缆引至配电箱、柜或控制屏、台的开孔部位。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]