[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937256":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937256,605,1,"单选题","某单位对其内部的低压配电和控制电器防火措施进行了检查，发现如下情况，其中不符合相关规范要求的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","接线端子接线采用有电镀金属层防锈的螺栓和螺钉连接",false,{"key":16,"text":17,"correct":14},"B","调阅资料发现控制柜内的接触器每月检查维修一次",{"key":19,"text":20,"correct":14},"C","配电柜金属外壳、框架的接地（P体采用镀锌扁钢",{"key":22,"text":23,"correct":24},"D","低压配电柜一个端子上连接2根导线，且2根导线线径不同",true,"2020新教材P372 低压配电与控制电器的同一端子上导线连接不应多于2根，且2根导线线径相同，防松垫圈等部件齐全；进出线接线正确；接线应采用铜质或有电镀金属层防锈的螺栓和螺钉连接，连接应牢固，要有防松装置，电连接点应无过热、锈蚀、烧伤、熔焊等痕迹；金属外壳、框架的接零（PEN）或接地（PE）应连接可靠；套管、瓷件外部无破损、裂纹痕迹。针对接触器频繁分合的工作特点，应每月检查维修一次接触器各部件，紧固各触头，及时更换损坏的零件。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]