[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937234":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},937234,605,1,"单选题","应安装在有防爆隔墙的间隔内的变、配电站（室）是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","户内电压为10kV以上、总油量为60kg以下的充油设备",false,{"key":16,"text":17,"correct":18},"B","总油量为60-600kg者",true,{"key":20,"text":21,"correct":14},"C","总油量为600kg以上者",{"key":23,"text":24,"correct":14},"D","10kV及其以下者","2020新教材P370 本题考查的是防火防爆的检查。户内电压为10kV以上、总油量为60kg以下的充油设备，可安装在两侧有隔板的间隔内；总油量为60~600kg者，应安装在有防爆隔墙的间隔内；总油量为600kg以上者，应安装在单独的防爆间隔内。10kV及其以下的变、配电室不应设在爆炸危险环境的正上方或正下方。变电室与各级爆炸危险环境毗连，最多只能有两面相连的墙与危险环境共用。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]