[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937229":3},{"question":4,"library":29},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":27,"analysis":28},937229,605,2,"多选题","消防用电设备供电线路在电缆隧道时，须采取防火封堵措施的情况有（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","穿越不同的防火分区",true,{"key":16,"text":17,"correct":14},"B","穿越建筑物的外墙处",{"key":19,"text":20,"correct":14},"C","电缆隧道的隔墙处",{"key":22,"text":23,"correct":14},"D","管线进出竖井处",{"key":25,"text":26,"correct":14},"E","沿竖井垂直敷设穿越楼板处","ABCDE","2020新教材P368 消防用电设备供电线路在电缆隧道、电缆桥架、电缆竖井、封闭式母线、线槽安装等处时，在下列情况下应采取防火封堵措施。1）穿越不同的防火分区。2）沿竖井垂直敷设穿越楼板处。3）管线进出竖井处。4）电缆隧道、电缆沟、电缆间的隔墙处。5）穿越建筑物的外墙处。6）至建筑物的人口处，至配电间、控制室的沟道人口处。7）电缆引至配电箱、柜或控制屏、台的开孔部位。",{"id":6,"name":30,"category":31,"favorite":32},"消防技术综合能力(一级、二级)","建筑工程",0]