[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937226":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937226,605,2,"多选题","下列属于预防电气线路接触电阻过大的措施是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","严禁滥用铜丝、铁丝代替熔断器的熔丝",false,{"key":16,"text":17,"correct":18},"B","铜、铝线相接，采用铜铝过渡接头",true,{"key":20,"text":21,"correct":14},"C","在线路上安装断路器或熔断器",{"key":23,"text":24,"correct":14},"D","根据负载情况，选择合适的电线",{"key":26,"text":27,"correct":18},"E","通过较大电流的接头，采用油质或氧焊接头","BE","2020新教材P374 预防电气线路接触电阻过大的措施有：导线与导线、导线与电气设备的连接必须牢固可靠；铜、铝线相接，宜采用铜铝过渡接头，也可采用在铜线接头处搪锡；通过较大电流的接头，应采用油质或氧焊接头，在连接时加弹力片后拧紧；要定期检查和检测接头，防止接触电阻增大，对重要的连接接头要加强监测。根据负载情况，选择合适的电线，严禁滥用铜丝、铁丝代替熔断器的熔丝属于预防电气线路过负荷的措施。在线路上安装断路器或熔断器属于预防电气线路短路的措施。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]