[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937225":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937225,605,2,"多选题","下列关于各类配电保护装置的说法，正确的有（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","过电流防护电器的额定电流或整定电流不应小于回路的计算负载电流",true,{"key":16,"text":17,"correct":14},"B","过电流防护电器的额定电流或整定电流不应大于回路的允许持续载流量",{"key":19,"text":20,"correct":14},"C","短路防护电器的遮断容量不应小于其安装位置处的预期短路电流",{"key":22,"text":23,"correct":14},"D","被保护回路内任一点发生短路时，短路防护电器都应在被保护回路的导体温度上升到允许限值前切断电源",{"key":25,"text":26,"correct":27},"E","漏电保护器的过载和短路保护特性允许用户在允许范围内自行调节",false,"ABCD","2020新教材P372 过电流防护电器的额定电流或整定电流不应小于回路的计算负载电流；过电流防护电器的额定电流或整定电流不应大于回路的允许持续载流量。短路防护电器的遮断容量不应小于其安装位置处的预期短路电流。被保护回路内任一点发生短路时，防护电器都应在被保护回路的导体温度上升到允许限值前切断电源。漏电保护器的漏电、过载和短路保护特性均由制造厂调整好，不允许用户自行调节。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]