[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937218":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937218,605,2,"多选题","（ ）的消防用电设备及消防电梯等的供电设备，应在其配电线路的最末一级配电箱处设置自动切换装置。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","消防控制室",true,{"key":16,"text":17,"correct":14},"B","消防水泵房",{"key":19,"text":20,"correct":14},"C","防烟和排烟风机房",{"key":22,"text":23,"correct":24},"D","消防应急照明",false,{"key":26,"text":27,"correct":24},"E","疏散指示系统","ABC","2020新教材P367 消防控制室、消防水泵房、防烟和排烟风机房的消防用电设备及消防电梯等的供电设备，应在其配电线路的最末一级配电箱处设置自动切换装置。水泵控制柜、风机控制柜等消防电气控制装置不应采用变频启动方式。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]