[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937186":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937186,605,1,"单选题","下列关于防烟排烟系统调试的说法，不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","当任何一个常闭送风口开启时，相应的送风机均应能联动启动",false,{"key":16,"text":17,"correct":14},"B","排烟防火阀在280℃时应自行关闭，并应连锁关闭排烟风机和补风机",{"key":19,"text":20,"correct":14},"C","有补风要求的机械排烟场所，当火灾确认后，补风系统应启动",{"key":22,"text":23,"correct":24},"D","当火灾自动报警探测器发出火警信号后，应在30s内启动与设计要求一致的送风口、送风机",true,"2020新教材P362 当任何一个常闭送风口开启时，相应的送风机均应能联动启动，A选项正确；根据5.2.2-5，排烟防火阀在280℃时应自行关闭，并应连锁关闭排烟风机和补风机，B选项正确；根据7.3.2-3，有补风要求的机械排烟场所，当火灾确认后，补风系统应启动，C选项正确；根据7.3.1-2，与火灾自动报警系统联动调试时，当火灾自动报警探测器发出火警信号后，应在15s内启动与设计要求一致的送风口、送风机，D选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]