[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937185":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},937185,605,1,"单选题","下列关于排烟防火阀的安装要求，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","阀门应顺气流方向关闭",false,{"key":16,"text":17,"correct":18},"B","防火分区隔墙两侧的排烟防火阀距墙端而不应大于150mm",true,{"key":20,"text":21,"correct":14},"C","应设独立的支、吊架",{"key":23,"text":24,"correct":14},"D","排烟防火阀安装完毕后应按各系统不小于30%的数量检查","2020新教材P358 排烟防火阀的安装应符合下列规定：1）型号、规格及安装的方向、位置应符合设计要求。2）阀门应顺气流方向关闭，防火分区隔墙两侧的排烟防火阀距墙端面不应大于200mm。3）手动和电动装置应灵活、可靠，阀门关闭严密。4）应设独立的支、吊架，当风管采用不燃材料防火隔热时，阀门安装处应有明显标识。检查数量：各系统按不小于30%检查。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]