[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937184":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937184,605,1,"单选题","对某民用建筑内设置的防烟排烟系统进行检查，下列检查结果中，不符合规范要求的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","金属风管采用法兰连接，其螺栓孔的间距为140mm",false,{"key":16,"text":17,"correct":14},"B","排烟风管的隔热层采用厚度为42mm的不燃绝热材料",{"key":19,"text":20,"correct":14},"C","非金属风管采用法兰连接，其螺栓孔的间距为115mm",{"key":22,"text":23,"correct":24},"D","金属风管应以板材连接的密封为主，可辅以密封胶嵌缝或其他方法密封，密封面宜设在风管的负压侧",true,"2020新教材P355 金属风管采用法兰连接时，其螺栓孔的间距不得大于150mm，A选项正确；根据6.3.1-5，排烟风管的隔热层应采用厚度不小于40mm的不燃绝热材料，B选项正确；根据6.3.2-2，非金属风管采用法兰连接，其螺栓孔的间距为115mm，C选项正确；根据6.3.1-3，金属风管应以板材连接的密封为主，可辅以密封胶嵌缝或其他方法密封，密封面宜设在风管的正压侧，D选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]