[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937183":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937183,605,1,"单选题","下列关于防排烟系统的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","系统柔性短管的制作材料必须为不燃材料",true,{"key":16,"text":17,"correct":18},"B","吊顶内的排烟管道与可燃物应保持不小于100mm的距离",false,{"key":20,"text":21,"correct":18},"C","防火分区隔墙两侧的排烟防火阀，距墙端面不应大于100mm",{"key":23,"text":24,"correct":18},"D","排烟口距可燃构件的距离不应小于1.0m","2020新教材P358 （7）吊顶内的排烟管道应采用不燃材料隔热，并应与可燃物保持不小于150mm的距离。 （2）阀门应顺气流方向关闭，防火分区隔墙两侧的排烟防火间，距墙端面不应大于200mm。 （2）排烟口距可燃物或可燃构件的距离不应小于1.5m。 （4）风管与风机的连接宜采用法兰连接，或采用不燃材料的柔性短管连接。若风机仅用于防烟、排烟时，则不宜采用柔性连接。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]