[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937180":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937180,605,1,"单选题","某大型综合楼有50层，设有机械加压送风系统。相关消防部门对机械防烟系统进行验收，下列验收方法及结果不符合要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","选取送风最不利的三个连续楼层模拟起火层及其上下层",false,{"key":16,"text":17,"correct":14},"B","避难层（间）仅选取本层",{"key":19,"text":20,"correct":21},"C","防烟楼梯间和前室的测试可同时进行",true,{"key":23,"text":24,"correct":14},"D","楼梯间与走道之间的压差为40Pa","2020新教材P364 （五）机械防烟系统的主要性能参数验收 （ 1 ）选取送风系统末端所对应的送风最不利的三个连续楼层模拟起火层及其上下层，封闭 避难层（间）仅需选取本层，测试前室及封闭避难层（间）的风压值及疏散门的门洞断面风速 值，应分别符合相关规范规定且偏差不大于设计值的 10% 。 （ 2 ）对楼梯间和前室的测试应单独分别进行，且五不影响。 （ 3 ）测试楼梯间和前室疏散门的门洞断面风速时，应同时开启三个楼层的疏散门。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]