[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937163":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937163,605,2,"多选题","下列有关部件的安装要求正确的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","排烟口距可燃物或可燃构件的距离不应小于1.5m",true,{"key":16,"text":17,"correct":14},"B","常闭送风口、排烟阀（口）的手动驱动装置应固定安装在明显可见、距楼地面1.3-1.5m之间便于操作的位置",{"key":19,"text":20,"correct":14},"C","活动挡烟垂壁与建筑结构（柱或墙）面的缝隙不应大于60mm",{"key":22,"text":23,"correct":24},"D","由两块或两块以上的挡烟垂帘组成的连续性挡烟垂壁，各块之间不应有缝隙，搭接宽度不应小于150mm",false,{"key":26,"text":27,"correct":24},"E","活动挡烟垂壁的手动操作按钮应固定安装在便于操作、明显可见处距楼地面1.0-1.5m之间","ABC","2020新教材P359 本题考查的是部件的安装。D错，由两块或两块以上的挡烟垂帘组成的连续性挡烟垂壁，各块之间不应有缝隙，搭接宽度不应小于100mm;E错，活动挡烟垂壁的手动操作按钮应固定安装在便于操作、明显可见处距楼地面1.3-1.5m之间。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]