[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937154":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937154,605,1,"单选题","防排烟系统的维护管理是系统正常完好、有效使用的基本保障，下列关于防烟排烟系统维护管理的说法，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","每周应对排烟风机的供电线路进行检查",true,{"key":16,"text":17,"correct":18},"B","每季度应对活动挡烟垂壁进行一次功能检测启动试验",false,{"key":20,"text":21,"correct":18},"C","每半年应对全部排烟防火阀进行自动和手动启动试验一次",{"key":23,"text":24,"correct":18},"D","每年应对全部防烟、排烟系统进行一次联动试验和性能检测","2020新教材P365 每季度应对防烟、排烟风机、活动挡烟垂壁、自动排烟窗进行一次功能检测启动试验及供电线路检查，检查方法应符合本标准第7.2.3条第7.2.5条的规定，A选项错误，B选项正确；根据9.0.4，每半年应对全部排烟防火阀、送风阀或送风口、排烟阀或排烟口进行自动和手动启动试验一次，检查方法应符合本标准第7.2.1条、第7.2.2条的规定，C选项正确；根据9.0.5，每年应对全部防烟、排烟系统进行一次联动试验和性能检测，其联动功能和性能参数应符合原设计要求，检查方法应符合本标准第7.3节和第8.2.5条第8.2.7条的规定，D选项正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]