[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937150":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937150,605,1,"单选题","下列关于防烟排烟系统组件的安装要求，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","排烟口距可燃物或可燃构件的距离不应小于0.5m",true,{"key":16,"text":17,"correct":18},"B","排烟窗的手动开启机构或按钮应固定安装在距楼地面1.3m~1.5m之间，并应便于操作、明显可见",false,{"key":20,"text":21,"correct":18},"C","活动挡烟垂壁的手动操作按钮应固定安装在距楼地面1.3m~1.5m之间便于操作、明显可见处",{"key":23,"text":24,"correct":18},"D","常闭送风口的手动驱动装置应固定安装在明显可见、距楼地面1.3m~1.5m之间便于操作的位置","2020新教材P358 排烟口距可燃物或可燃构件的距离不应小于1.5m，A选项错误；根据6.4.5-3，排烟窗的手动开启机构或按钮应固定安装在距楼地面1.3m～1.5m之间，并应便于操作、明显可见，B选项正确；根据6.4.4-3，活动挡烟垂壁的手动操作按钮应固定安装在距楼地面1.3m～1.5m之间便于操作、明显可见处，C选项正确；根据6.4.3，常闭送风口、排烟阀或排烟口的手动驱动装置应固定安装在明显可见、距楼地面1.3m～1.5m之间便于操作的位置，D选项正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]