[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937145":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937145,605,1,"单选题","防排烟系统施工安装前，对风管阀（口）进行现场检验时，下列检查项目中，不属于现场检查项目的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","电动防火阀",false,{"key":16,"text":17,"correct":14},"B","送风口",{"key":19,"text":20,"correct":21},"C","正压送风机",true,{"key":23,"text":24,"correct":14},"D","柔性短管","2020新教材P354 （二）阀口检查要求 （ 1 ）排烟防火阀、送风口、防烟阀、排烟阀或排烟口等符合有关消防产品标准的规定，其型号、规格应符合设计要求，手动开启灵活、关闭可靠严密。 （ 2 ）防火阀、送风口和排烟阀或排烟口等的驱动装置，动作应可靠，在最大工作压力下工作正常。（ 3 ）防烟、排烟系统柔性短管的制作材料必须为不燃材料。 题目问的是风管部件，那唯独选项C不属于风管阀（口）的部件，而是风系统的部件，故C错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]