[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937124":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937124,605,2,"多选题","下列关于减压阀的设置与应用正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","减压阀应设置在报警阀组后，当连接两个及以上报警阀组时，应设置备用减压阀。",false,{"key":16,"text":17,"correct":14},"B","减压阀的进口处应设置过滤器，过滤器的孔网直径不宜小于4~5目\u002Fcm2，过流面积不应小于管道截面面积的2倍。",{"key":19,"text":20,"correct":21},"C","过滤器和减压阀前后应设压力表，压力表的表盘直径不应小于100mm，最大量程宜为设计压力的2倍。",true,{"key":23,"text":24,"correct":14},"D","比例式减压阀宜水平安装，可调式减压阀宜垂直安装。",{"key":26,"text":27,"correct":21},"E","减压阀应设置流量检测测试接口或流量计","CE","参考《消防给水及消火栓系统技术规范》83.4：减压阀的设置应符合下列规定：1.减压阀应设置在报警阀组入口前，当连接两个及以上报警阀组时，应设置备用减压阀：选项A说设置在报警阀组后，故A错误。2.减压阀的进口处应设置过滤器，过滤器的孔网直径不宜小于4目\u002Fcm2~5目\u002Fcm2，过流面积不应小于管道截面积的4倍；故B错误。3.过滤器和减压阀前后应设压力表，压力袁的表盘直径不应小于100mm，最大量程宜为设计压力的2倍；故C正确。6.减压阀应设置流量检测测试接口或流量计；故E正确。8.比例式减压阀宜垂直安装，可调式减压阀宜水平安装：故D错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]