[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937115":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937115,605,2,"多选题","下列关于消防水泵的叙述中，（ ）是正确的。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","一组消防水泵应设不少于2条的输水干管与消防给水环状给水管网连接，当其中一条输水管检修时，其余输水管应仍能供应全部消防给水设计流量",true,{"key":16,"text":17,"correct":14},"B","一组消防水泵，吸水管不应少于2条。当其中一条损坏或检修时，其余吸水管应仍能通过全部设计流量",{"key":19,"text":20,"correct":21},"C","消防水泵的吸水管上应设置明杆闸阀或暗杆蝶阀，但当设置暗杆阀门时应设有开启刻度和标志；当管径超过DN300时，宜设置电动阀门",false,{"key":23,"text":24,"correct":14},"D","消防水泵的出水管上应设置止回阀、明杆闸阀；当采用蝶阀时，应带有自锁装置",{"key":26,"text":27,"correct":14},"E","消防水泵的吸水管穿越消防水池时，应采用柔性套管；采用刚性防水套管时应在水泵吸水管上设置柔性接头，且管径不应大于DN150","ABDE","参考《消防给水及消火栓系统技术规范》5.1.13可知，ABDE正确，C选项的“暗杆蝶阀”错误，应为“带自锁装置的蝶阀”，故C错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]