[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937112":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937112,605,2,"多选题","下列关于水幕喷头布置的叙述中，（ ）是正确的。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","防火分隔水幕采用水幕喷头时，喷头不应少于3排",true,{"key":16,"text":17,"correct":14},"B","防火分隔水幕采用开式洒水喷头时，喷头不应少于2排",{"key":19,"text":20,"correct":21},"C","防护冷却水幕的喷头宣布置成2排",false,{"key":23,"text":24,"correct":14},"D","防火分隔水幕的喷头布置，应保证水幕的宽度不小于6m",{"key":26,"text":27,"correct":21},"E","防火分隔水幕不宜用于尺寸为16m（宽）x8m（高）的舞台口","ABD","选项A、B、C、D，参考《喷规》7.1.15：“防火分隔水幕的喷头布置，应保证水幕的宽度不小于6m。采用水幕喷头时，喷头不应少于3排；采用开式洒水喷头时，喷头不应少于2排。防护冷却水慕的喷头宜布置成单排”，故A、B、D正确，C错误；选项E，参考《喷规》4.2.10：“防护冷水水幕应直接将水喷向被保护对象；防火分隔水幕不宜用于尺寸超过15m（宽）×8m（高）的开口（舞台口除外）”，故E错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]