[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937111":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937111,605,2,"多选题","某工程室内消火栓水泵（一用一备）流量为40L\u002Fs，扬程为100m，以下关于消火栓泵组的叙述错误的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","该泵组应预留测量用流量计",true,{"key":16,"text":17,"correct":18},"B","流量检测装置最大量程为94L\u002Fs",false,{"key":20,"text":21,"correct":18},"C","压力检测装置的最大量程为230m",{"key":23,"text":24,"correct":18},"D","每台消防水泵出水管上应设置DN65的试水管，并应采取排水措施",{"key":26,"text":27,"correct":14},"E","该泵组应预留测量用压力计接口","AE","参考《消防给水及消火栓系统技术规范》5.1.11：“一组消防水泵应在消防水泵房内设置流量和压力测试装置，并应符合下列规定：1.单台消防水泵的流量不大于20L\u002Fs、设计工作压力不大于0.50MPa时，泵组应预留测量用流量计和压力计接口，其他泵组宜设置泵组流量和压力测试装置；故A、E错误；2.消防水泵流量检测装置的计量精度应为0.4级，最大量程的75%应大于最大一台消防水泵设计流量值的175%；94×75%=70.5m＞40×175%=70m，故B正确；3.消防水泵压力检测装置的计量精度应为0.5级，最大量程的75%应大于最大一台消防水泵设计压力值的165%：230×75%=172.5m＞100×165%=165m，故C正确；4.每台消防水泵出水管上应设置DN65约试水管，并应采取排水措施”，故D正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]