[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937106":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937106,605,2,"多选题","下列关于利用有压气体作为系统启动介质的干式系统、预作用系统的叙述中，正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","干式系统配水管道内充入有压气体的目之一是将有压气体作为传递火警信号的介质",true,{"key":16,"text":17,"correct":14},"B","干式系统配水管道内充入有压气体的目之一是防止干式报警阀误动作",{"key":19,"text":20,"correct":21},"C","常规的预作用系统配水管道内充入有压气体的目之一是将有压气体作为传递火警信号的介质",false,{"key":23,"text":24,"correct":14},"D","常规的预作用系统配水管道内充入有压气体的目之一是将有压气体作为监测管道严密性的介质",{"key":26,"text":27,"correct":21},"E","利用有压气体检测管道是否严密的预作用系统，配水管道内的气压值不宜小于0.03MPa，且不宜大于0.10MPa","ABD","选项A、B、C、D，参考《自喷》5.0.12条文说明：“干式系统配水管道内充入有压气体的目的，一是将有压气体作为传递火警信号的介质，二是防止干式报警阀误动作；常规的预作用系统，其配水管道维持一定气压的目的，不同于早式系统，是将有压气体作为监测管道严密性的介质”，故A、B、D正确：选项E，参考《自喷》5.0.12：“利用有压气体检测管道是否严密的预作用系统，配水管道内的气压值不宜小于0.03MPa，且不宜大于0.05MPa”，故E错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]