[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937090":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937090,605,2,"多选题","下列关于消防控制室内设备布置中不符合相关规定的是（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","设备面盘前的操作距离单列布置时不应小于1m;双列布置时不应小于2m",true,{"key":16,"text":17,"correct":14},"B","在值班人员经常工作的一面，设备面盘至墙的距离不应小于2m",{"key":19,"text":20,"correct":14},"C","设备面盘后的维修距离不宜小于1.5m",{"key":22,"text":23,"correct":14},"D","设备面盘的排列长度大于4m时，其两端应设置宽度不小于1.2m的通道",{"key":25,"text":26,"correct":27},"E","与建筑其他弱电系统合用的消防控制室内，消防设备应集中设置",false,"ABCD","GB50116-2013 火灾自动报警系统设计规范 3.4.8：消防控制室内设备的布置应符合下列规定：1.设备面盘前的操作距离，单列布置时不应小于1.5m：双列布置时不应小于2m。2.在值班人员经常工作的一面，设备面盘至墙的距离不应小于3m。3.设备面盘后的维修距离不宜小于1m。4.设备面盘的排列长度大于4m时，英两端应设置宽度不小于1m的通道。5.与建筑其他弱电系统合用的消防控制室内，消防设备应集中设置，并应与其他设备间有明显间隔。故A、B、C、D均错误，E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]