[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937087":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937087,605,2,"多选题","湿式系统和干式系统的联动控制设计时，（ ）的动作信号应反馈至消防联动控制器。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","水流指示器",true,{"key":16,"text":17,"correct":14},"B","信号阀",{"key":19,"text":20,"correct":14},"C","压力开关",{"key":22,"text":23,"correct":14},"D","喷淋消防泵的启动和停止的动作信号",{"key":25,"text":26,"correct":27},"E","末端试水装置",false,"ABCD","GB50116-2013 火灾自动报警系统设计规范 4.2.1：“湿式系统和干式系统的联动控制设计，应符合下列规定：3水流指示器、信号阀、压力开关、喷淋消防泵的启动和停止的动作信号应反馈至消防联动控制器”，故ABCD正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]