[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937085":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937085,605,2,"多选题","下列关于火灾自动报警系统设备设置的说法中不正确是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","火灾报警控制器和消防联动控制器安装在墙上时，其主显示屏高度宜为1.5m～1.8m",false,{"key":16,"text":17,"correct":18},"B","点型探测器至空调送风口边的水平距离不应小于Im，并宜接近回风口安装。探测器至多孔送风顶棚孔口的水平距离不应小于0.5m",true,{"key":20,"text":21,"correct":18},"C","手动火灾报警按钮应设置在明显和便于操作的部位。当采用壁挂方式安装时，其底边距地高度宜为1.1m～1.3m，且应有明显的标志",{"key":23,"text":24,"correct":18},"D","当火灾警报器采用壁挂方式安装时，其底边距地面高度应大于2m",{"key":26,"text":27,"correct":14},"E","壁挂扬声器的底边距地面高度应大于2.2m","BCD","GB 50116-2013 火灾自动报警系统设计规范 6.1.3：“火灾报警控制器和消防联动控制器安装在墙上时，其主显示屏高度宜为1.5m～1.8m，其靠近门轴的侧面距墙不应小于0.5m，正面操作距离不应小于1.2m”，故A正确：选项B，6.2.8：“点型探测器至空调送风口边的水平距离不应小于1.5m，并宜接近回风口安装。探测器至多孔送风顶棚孔口的水平距离不应小于0.5m”，故B错误：选项C，6-3.2：“手动火灾报警按钮应设置在明显和便于操作的部位。当采用壁挂方式安装时，其底边距地高度宜为1.3m～1.5m，且应有明显的标志”，故C错误：选项D，6.5.3：“当火灾警报器采用壁挂方式安装时，其底边距地面高度应大于2.2m”，故D错误；选项E，6.6.2：“壁挂扬声器的底边距地面高度应大于2.2m”，故E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]