[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937070":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937070,605,2,"多选题","对于灭火器的配置要求正确的是（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","一个计算单元内配置的灭火器数量不得少于2具",true,{"key":16,"text":17,"correct":14},"B","每个设置点的灭火器数量不宜多于5具",{"key":19,"text":20,"correct":14},"C","灭火器配置的设计与计算应按计算单元进行",{"key":22,"text":23,"correct":14},"D","每个灭火器设置点实配灭火器的灭火级别和数量不得小于最小需配灭火级别和数量的计算值",{"key":25,"text":26,"correct":27},"E","灭火器设置点的位置和数量应根据灭火器的最小保护距离确定，并应保证最不利点至少在1具灭火器的保护范围内",false,"ABCD","GB 50140-2005 灭火器配置设计规范 6.1.1：“一个计算单元内配置的灭火器数量不得少于2具”，故A正确：选项B，6.1.2：“每个设置点的灭火器数量不宜多于5具”，故B正确；选项C，7.1.1：“灭火器配置的设计与计算应按计算单元进行。灭火器最小需配灭火级别和最少需配数量的计算值应进位取整”，故C正确：选项D，7.1.2：“每个灭火器设置点实配灭火器的灭火级别和数量不得小于最小需配灭火级别和数量的计算值”，故D正确；7.1-3：“灭火器设置点的位置和数量应根据灭火器的最大保护距离确定，并应保证最不利点至少在1具灭火器的保护范围内”，故E错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]