[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937062":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937062,605,2,"多选题","下列关于室内消防管网及附件的叙述中，（ ）是错误的。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","厂房检修停止使用的消火栓不应超过5个",true,{"key":16,"text":17,"correct":14},"B","多层民用建筑室内消防给水管道上阀门的布置应保证检修管道时关闭的竖管不超过1根，但设置的竖管超过3根时，可关闭2根",{"key":19,"text":20,"correct":21},"C","高层住宅应保证检修管道时关闭停用的竖管不超过一根。当竖管超过4根时，可关闭不相邻的两根",false,{"key":23,"text":24,"correct":21},"D","高层公共建筑裙房内消防给水管道的阀门布置适用《建筑设计防火规范》",{"key":26,"text":27,"correct":14},"E","当室内消火栓给水管网与自动喷水合用消防泵时，供水管路沿水流方向应在报警阀后分开设置","ABE","选项A.《消防给水及消火栓系统技术规范》并无相关要求，故A错误；选项B和C，参考《消防给水及消火栓系统技术规范》8.1.6可知，B错误，C正确；选项D，所有公其建筑消防给水管道的阀门布置都适用《建规》，故D正确；选项E，参考＜消规》8.1.7：“室内消火栓给水管网宜与自动喷水等其他水灭火系统的管网分开设置；当合用消防泵时，供水管路沿水流方向在报警阀前分开设置”，故E错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]