[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937061":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937061,605,1,"单选题","在对火灾自动报警控制器进行调试时，在完成主、备电源的自动转换后，应在备电工作状态检查控制器的负载功能。此时，控制器备用电源容量应能保证控制器在监视状态下工作8h后，尚应在负载功能试验期间工作（ ）min。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","30",true,{"key":16,"text":17,"correct":18},"B","60",false,{"key":20,"text":21,"correct":18},"C","90",{"key":23,"text":24,"correct":18},"D","120","检查主、备电源的自动转换功能，并在备电工作状态下重复控制器的负载功能检查。根据《火灾报警控制器》GB 4717 - 2005 5.2.10.3，备用电源在放电至终止电压条件下，充电24h，其容量应可提供控制器在监视状态下工作8h后，在不少于10只的火灾探测器同时处于火灾报警状态下工作30min。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]