[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937060":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937060,605,2,"多选题","某建筑高度为23.8m的4层商业建筑，对其进行室内消火栓的配置和设计中，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","选用DN65的室内消火栓",true,{"key":16,"text":17,"correct":18},"B","消火栓栓口动压大于0.5MPa",false,{"key":20,"text":21,"correct":14},"C","消火栓栓口动压不小于0.25MPa",{"key":23,"text":24,"correct":18},"D","配置直径65mm长30m的消防水带",{"key":26,"text":27,"correct":14},"E","水枪充实水柱不小于10m","ACE","选项A、D，参考《消防给水及消火栓系统技术规范》7.4.2：“室内消火栓的配置应符合下列要求：1应采用DN65室内消火栓，并可与消防软管卷盘或轻便水龙设置在同一箱体内；2应配置公称直径65有内衬里的消防水带，长度不宜超过25.0m；”故A正确、D错误。选项B、C、E，参考《消防给水及消火栓系统技术规范》7.4.12：“室内消火栓栓口压力和消防水枪充实水柱，应符合下列规定：1.消火栓栓口动压力不应大于0.50MPa；当大于0.70MPa时必须设置减压装置；2.高层建筑、厂房、库房和室内净空高度超过8m的民用建筑等场所，消火栓栓口动压不应小于0.35MPa，且 消防水枪充实水柱应按13m计算；其他场所，消火栓栓口动压不应小于0.25MPa，且消防水枪充实水柱应按10m计算”。故B错误，C、E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]