[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937052":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937052,605,1,"单选题","施工完成后对报警阀组调试时错误的有（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","湿式报警阀调试时，在试水装置处放水，压力表测得当湿式报警阀进口水压大于0.14MPa、流量计读数显示放水流量大于1L\u002Fs时，报警阀启动",false,{"key":16,"text":17,"correct":14},"B","湿式报警阀组的水力警铃在秒表读数12s时发出报警铃声",{"key":19,"text":20,"correct":21},"C","干式报警阀调试时，开启系统试验阀，水流到试验装置出口所需时间为5min",true,{"key":23,"text":24,"correct":14},"D","雨淋阀调试时，当报警水压为0.05MPa，水力警铃发出报警铃声","选项A、B、D，参考《自动喷水灭火系统施工及验收规范》7.2.5：报警阀调试应符合下列要求：1.湿式报警阀调试时，在试水装置处放水，当湿式报警阀进口水压大于0.14MPa、放水流量大于1L\u002Fs时，报警阀应及时启动：带延迟器的水力警铃应在5~90s内发出报警铃声，不带延迟器的水力警铃应在15s内发出报警铃声；压力开关应及时动作，并反馈信号。故A、B正确：3.雨淋阀调试宜利用检测、试验管道进行。自动和手动方式启动的雨淋阀，应在15s之内启动；公称直径大于200mm的雨淋阀调试时，应在60s之内启动。雨淋阀调试时，当报警水压为0.05MPa，水力警铃应发出报警铃声。故D正确：选项C，参考《喷规》8.0.9：“干式系统的配水管道充水时间，不宜大于1min；预作用系统与雨淋系统的配水管道充水时间，不宜大于2min”，故C错误；",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]